TB 9-6115-643-13
OVER VOLTAGE
CHECK BATTERY CHARGING
YES
IS BATTERY VOLTAGE GREATER
CIRCUIT FOR PROPER
THAN +30VDC?
OPERATION (REFER TO
TM 9-6115-643-24)
NON-START
NOT OK
ADD FUEL
CHECK FUEL LEVEL
OK
NOTIFY NEXT HIGHER LEVEL
NOT OK
OF MAINTENANCE TO
CHECK FOR DAMAGED WIRING
REPLACE OR REPAIR WIRING
HARNESS
OK
NOT OK
CHECK FOR VOLTAGE PULSES AT
REPLACE CONTROL UNIT
FUEL PUMP
OK
NOT OK
REPLACE FUEL PUMP
CHECK FOR FUEL PUMP OPERATION
OK
NOT OK
REPLACE GLOW PLUG
REPLACE HEATER