TM 9-6150-226-13
Section IV.
OPERATIONS UNDER UNUSUAL CONDITIONS
Section Index
Subject
Page
Emergency Procedures
2-60
Nuclear, Biological and Chemical (NBC) Decontamination Procedures
2-60
Operation in
Operation in
Operation in
Operation in
Operation in
o
o
o
o
o
Dusty or Sandy Areas
Extreme Cold
Extreme Heat
Rainy or Humid Conditions
Saltwater Areas
2-58
2-58
2-59
2-58
2-59
WARNING
High Voltage is present in
supports
equipment
u s i n g
this system.
DISE and PDISE
120/208 V ac.
Ground the
generator set.
Death or severe injury may result if you do
not properly ground the generator set.
The DISE feeder/distribution centers use ground
fault circuit breakers.
The neutral and ground
of some generator
sets must be electrically
connected with 6-gage wire for the ground fault
circuit breakers to function properly.
Failure
to electrically connect the ground and neutral
lugs may result in death or severe injury.
Do not rely on the color of the wire insulation
for phase color-coding.
The insulation on the
wires inside the cable jacket may vary, depending
on the supplier.
Wires will be color coded to
designate the phases.
Perform a continuity test
to verify correct phase designation in accordance
with the identified color.
Connect the pigtail ground leads to the generator
set.
Death or severe injury may result if you do
not properly connect the ground leads of the
pigtail cables to the generator set.
Do not submerge feeder/distribution centers or
cable connector in water.
Death or severe injury
may result.
2-57