TM 9-6150-226-13
g. L1, L2, and L3 Phase Indicator Lights.
These lights (6, Figure 2-1)
and (5. Figure 2-2) for M200 A/P are connected between neutral and
each phase.
When electricalpower is being supplied to the feeder center, the
lights will illuminate.
2-2. M1OO DISE FEEDER CENTER AND M1OO A/P PDISE FEEDER CENTER.
a.
Main Circuit Breaker CB1 (100-amp,3-Phase).
This 3-phase circuit
breaker (1, Figure 2-3) for M1OO and (1, Figure 2-4) for M1OO A/P is in series
between the 100-amp input connector and the bus bars.
This circuit breaker
prevents input power to the distribution center from exceeding a total current
of 100 amps per phase (36 kW maximum load).
This circuit breaker also allows
the operator to turn off power to all output circuit breakers.
b.
CB3 and CB6 (60-amp,3-Phase).
Each 3-phase circuit breaker (2,
Figure 2-3) for M1OO and (2, Figure 2-4) for M1OO A/P is in series between the
bus bars and a 60-amp output connector.
These circuit breakers prevent output
power to the connectors from exceeding a current of 60 amps per phase (21.6 kW
maximum load).
These circuit breakers also allow the operator to turn off
power to the load circuits.
2-3