TM 9-6150-226-13WARNINGHigh voltage is present in this system. DISE andPDISE supports equipment using 120/208 V ac. Donot rely on the color of the wire insulation forphase color-coding.The insulation on the wiresinside the cable jacket may vary, depending onthe supplier.Wires will be marked with coloredtape to designate the phases.Perform acontinuitytest toverifycorrectphasedesignation in accordance with the colored tape.NOTES :1.ALL DIMENSIONS ARE IN INCHES, WITH THE METRIC EQUIVALENT IN PARENTHESES.2.CUT AND REMOVE CABLE AND WIRE INSULATION FROM CABLE ENDS AS INDICATED.3.TWIST FOUR GROUND WIRES TOGETHER.4.INSTALL P1 AND P2 CONNECTORS ON PROPER CABLE ENDS SO COLORS ANDPINS/SOCKETS MATCH AS FOLLOWS:COLORFROMTOBLACKP1-AP2-AREDP1-BP2-BBLUEP1-CP2-CWHITEP1-NP2-NGREEN (OR BARE)GREEN (OR BARE)P1-GP2-GGREEN (OR BARE)GREEN (OR BARE)5.VERIFY ELECTRICAL CONTINUITY FOR EACH “FROM-TO” PATH WITH AN OHMMETER.6.CRIMP PINS/SOCKETS TO CABLE WIRES.7.ASSEMBLE P1 AND P2 CONNECTORS SO -KEYS/KEYWAYS AND PINS/SOCKETS ALINE ASINDICATED.8.MARK SLEEVES IN ACCORDANCE WITH MIL-M-60903 AS FOLLOWS:97403-13226E7023-1120/208 VAC3 PHASE60 AMPFIGURE F-2.40/60-amp, 100-ft (30.5m) service/feeder cable. (sheet 3 of 3)F-11