TM 9-6150-226-13
WARNING
High voltage is present in this system. DISE and
PDISE supports equipment using 120/208 V ac. Do
not rely on the color of the wire insulation for
phase color-coding.
The insulation on the wires
inside the cable jacket may vary, depending on
the supplier.
Wires will be marked with colored
tape to designate the phases.
Perform a
continuity
test. to
verify
correct
phase
designation in accordance with the colored tape.
NOTES :
1.
ALL DIMENSIONS ARE IN INCHES, WITH THE METRIC EQUIVALENT IN PARENTHESES.
2.
CUT AND REMOVE CABLE AND WIRE INSULATION FROM CABLE ENDS AS INDICATED.
3.
TWIST FOUR GROUND WIRES TOGETHER.
4.
INSTALL P1 AND P2 CONNECTORS ON PROPER CABLE ENDS SO COLORS AND
PINS/SOCKETS MATCH AS FOLLOWS:
COLOR
FROM
TO
BLACK
P1-A
P2-A
RED
P1-B
P2-B
BLUE
P1-C
P2-C
WHITE
P1-N
P2-N
GREEN (OR BARE)
GREEN (OR BARE)
P1-G
P2-G
GREEN (OR BARE)
GREEN (OR BARE)
5.
VERIFY ELECTRICAL CONTINUITY FOR EACH FROM-TO PATH WITH AN OHMMETER.
6.
CRIMP PINS/SOCKETS TO CABLE WIRES.
7.
ASSEMBLE P1 AND P2 CONNECTORS SO KEYS/KEYWAYS AND PINS/SOCKETS ALINE AS
INDICATED.
8.
MARK SLEEVES IN ACCORDANCE WITH MIL-M-60903 AS FOLLOWS:
97403-13226E7023-3
120/208 VAC
3 PHASE
60 AMP
FIGURE F-1.
40/60-amp, 25-ft (7.6m) service/feeder cable. (sheet 3 of 3)
F - 8