REPROGRAMMING OR VERIFYING GSC SETPOINTS - Continued
Table 7. OP6 Spare Input/Output Setpoint Programming - Continued.
FACTORY
DESCRIPTION
RANGE OF VALUES
SETPOINTS
DEFAULT
0 Unused
0
0
SP17 Spare Indicator 1 Trigger
1 Active SP01 fault 3
Condition: The condition used by GSC
2 Active SP02 fault 3
to trigger Spare Indicator 1.
3 Active SP03 fault 3
4 Active SP04 fault 3
0
0
SP18 Spare Indicator 2 Trigger
5 Any combination
Condition: The condition used by GSC
of active SP01,
to trigger Spare Indicator 2.
SP02, SP03, or
SP04 faults 3
0
0
SP19 Spare Indicator 3 Trigger
6 Coolant loss fault 3
Indicator: The condition used by GSC to
7 High oil temperature
trigger Spare Indicator 3.
fault 3
1
The setpoints are programmed at the factory to the default value. The setpoints may be changed to satisfy
customer requirements or application requirements.
3
SP14 is programmed to 11 (CCM control), the spare output is always active low. When SP16 is programmed
to 11 (CCM control), the spare relay is always active when triggered.