TM 9-6115-730-24
PRELIMINARY CHECKS AND ADJUSTMENT OF EQUIPMENT - Continued
3. (US Army and Air Force) Perform Preventive Maintenance Checks and Services (PMCS) (TM 9-6115-
730-10).
4. If there is a recommended change to equipment technical publications, complete form DA 2028-2 and forward
it by email <AMSEL-LC-LEO-PUBS-CHG@mail1.Monmouth.army.mil>, fax to 732-532-3421, or mail to
Commander, U.S. Army Communications-Electronics Life Cycle Management Command, ATTN: AMSEL-LC-
LEO-D-CS-CFO, Fort Monmouth, New Jersey 07703-5000. For Air Force, use AFTO Form 22 in accordance
with TO 00-5-1 and mail directly to Commander, WR-ALC/LEET, Robins AFB, GA, 31098. You may also e-
mail your form to <http://wralc.tilta.afto@robins.af.mil>.
OUTPUT VOLTAGE SETTING
WARNING
Metal jewelry will conduct electricity. All jewelry can become entangled in generator set
components. Remove all jewelry when working on generator set. Failure to comply can cause
injury or death to personnel by electrocution.
DO NOT wear loose clothing when performing checks, services and maintenance. Failure to
comply can cause injury or death to personnel.
High voltage is produced when this generator set is in operation. Make sure unit is completely
shut down and free of any power source before attempting any repair or maintenance on the unit.
Failure to comply can cause injury or death to personnel.
DC voltages are present at generator set electrical components even with generator set shut
down. Avoid shorting any positive with ground/negative. Failure to comply can cause injury to
personnel and damage to equipment.
High voltage is produced when the generator set is in operation. Never attempt to start or
maintain the generator set unless it is properly grounded. Failure to comply can cause injury or
death to personnel.
1. Ensure generator set is fully stopped, ENGINE CONTROL switch is set to OFF/RESET, and DEAD CRANK
SWITCH is OFF before proceeding.
2. Set Battery Disconnect Switch to OFF.
3. Remove four nuts (Figure 1, Item 1), washers (Figure 1, Item 2), and clear protective panel (Figure 1, Item 3)
from the reconnection board.
4. Remove 12 nuts (Figure 1, Item 4) and reconnection board (Figure 1, Item 5).
5. Align the arrow on the reconnection board (Figure 1, Item 5) with the arrow on the base corresponding to the
desired generator output voltage(s).
0014-2