TM 9-6115-730-10
200 kW TACTICAL QUIET GENERATOR
0009 00
MALFUNCTION/SYMPTON INDEX Continued
Malfunction/Symptom
Work Package and Page No.
18.
AL8 Generator Under Voltage
Notify maintenance.
19.
Notify maintenance.
20.
AL10 Generator Under Frequency
Notify maintenance.
21.
AL11 Generator Reverse Power
Notify maintenance.
22.
AL12 Phase Over Current
Notify maintenance.
23.
AL13 Generator Total Over Current
Notify maintenance.
24.
AL14 Phase A No Voltage Input
Notify maintenance.
25.
AL15 GSC Configuration Error
Notify maintenance.
26.
AL16 Incorrect Phase Sequence
Notify maintenance.
27.
AL17- Improper Generator or Bus Voltage
28.
AL18 Synchronizer Time-out
GSC SP Fault Codes
29.
SP1 Low Fuel Level
Troubleshoot as Malfunction
30.
SP2 DVR fault
Notify maintenance.
31.
SP3 When relay K1 is energized and one or both of the following is true for
Notify maintenance.
more than 2 seconds an SP3 fault is announced:
0.2 Hz.
The difference in phase between the generator and the bus is greater than 10
degrees.
The GSC will then stop the synchronization process until the fault is cleared
and corrected.
32.
SP4 Input is active when 208 or 416 VAC is detected on the load bus by relay
Notify maintenance.
DBLO or DBHI.
This input is compared to the reading of the bus voltage (P7-17 and
P7-18).
If the voltage of phase A is less than 20% of the rated voltage, it is considered
to be "dead". If the condition of these measurements is different with regards
to presence or absence of bus voltage, a fault is announced.
DVR Alarm Fault Codes
33.
601 Internal Memory Failure Alarm
Notify maintenance.
34.
602 Internal Watchdog Failure Alarm
Notify maintenance.
35.
603 Rotating Diode Failure Alarm
Notify maintenance.
36.
604 Reverse VAR Alarm
Notify maintenance.
0009 00-2