TM 9-6115-729-24
0069
REMOVAL
1. Ensure generator set is fully stopped, ENGINE CONTROL switch is OFF/RESET, Battery Disconnect Switch is
OFF, and DEAD CRANK SWITCH is OFF before proceeding.
2. Open right rear doors and right front door.
3. Disconnect hose (Figure 1, Item 1) and reducer (Figure 1, Item 2) from bottom of crankcase ventilation filter
(Figure 1, Item 3).
4. Unlatch bowl (Figure 1, Item 4) from crankcase ventilator filter (Figure 1, Item 3) and remove filter element
(Figure 1, Item 5).
5. Wipe up any spilled oil.
END OF TASK
INSTALLATION
1. Install filter element (Figure 1, Item 5) and latch bowl (Figure 1, Item 4) back onto crankcase ventilation filter
(Figure 1, Item 3).
2. Install reducer (Figure 1, Item 2) on bottom of crankcase ventilation filter (Figure 1, Item 3) and install hose
(Figure 1, Item 1).
3. Close right rear doors and right front door.
0069-2