TM 9-6115-729-24
0010
TROUBLESHOOTING USING DVR FAULT CODES - Continued
CORRECTIVE ACTION - Continued
STEP 3.
Troubleshoot wiring harness.
a. Check and repair wiring between PT2, PT3 and DVR, as required
b. Check and repair wiring between PT2, PT3, and fuses F1, F2, and F3, as
c.
Check and repair wiring between fuses (F1, F2, and F3) and generator, as
d. Remove fuses F1, F2, and F3. Measure resistance between F1 terminal 2
and F2 terminal 2. If not 0.3 +/- 0.1 ohms, replace transformer PT2 (WP
e. Measure resistance between F2 terminal 2 and F3 terminal 2. If not 0.3 +/-
f.
Measure resistance between F3 terminal 2 and F1 terminal 2. If not 0.6 +/-
0.1 ohms, check all connections on transformers (WP 0052).
g. Measure resistance between J31-5 and J31-6. If not 0.3 +/- 0.1 ohms,
h. Measure resistance between J31-6 and J31-7. If not 0.3 +/- 0.1 ohms,
i.
On EMCP, set ENGINE CONTROL switch to OFF/RESET to clear bus fault.
STEP 4.
STEP 5.
Start generator set and measure AC voltage between pins A3-26 and A3-28, A3-
28 and A3-30, and A3-26 and A3-30. Verify 95 to 120 Vac present at all three
locations.
STEP 6.
STEP 7.
Measure AC voltage between pins A3-20 and A3-22, A3-22 and A3-24, and
A3-20 and A3-24. Verify 190 to 240 Vac present at all three locations.
b. If the problem is not resolved, replace the DVR (WP 0041).
STEP 8.
Verify the problem is resolved.
0010-11