TM 9-6115-729-10
100 kW TACTICAL QUIET GENERATOR SET
0006 00
OPERATION UNDER USUAL CONDITIONS Continued
PREPARATION FOR MOVEMENT
WARNING
Metal jewelry can conduct electricity and become entangled in generator set components. Remove
all metal jewelry when working on generator set. Failure to comply can cause injury or death to
personnel.
High voltage is produced when this generator set is in operation. Make sure unit is completely shut
down and free of any power source before attempting any repair or maintenance on the unit.
Failure to comply can cause injury or death to personnel.
DC voltages are present at generator set electrical components even with generator set shut down.
Avoid shorting any positive with ground/negative. Failure to comply can cause injury to personnel
and damage to equipment.
If necessary to move a generator set that has been operating in parallel with another generator set,
shut down all generator sets prior to removing load cables or ground. Failure to comply can cause
injury or death to personnel by electrocution.
Before making any connections for parallel operation or moving a generator set that has been
operating in parallel, ensure there is no input to the load board and the generator sets are shut
down. Failure to comply can cause injury or death to personnel by electrocution.
High voltage is produced when the generator set is in operation. Never attempt to connect or
disconnect load cables while the generator set is running. Failure to comply can cause injury or
death to personnel.
1.
Set ENGINE CONTROL switch to OFF/RESET.
2.
3.
Open rear left housing door and set DEAD CRANK SWITCH to OFF.
4.
Open battery compartment and set Battery Disconnect Switch to OFF.
5.
Open output load terminal door at right rear of TQG.
6.
Using terminal nut wrench (1), loosen load terminal nuts (2).
7.
Disconnect all load cables (3) from output load terminals (4) and remove cables from generator set and from all
8.
Secure wrench (1) inside load terminal door and close door.
0006 00-38