TM 9-6115-729-10
100 kW TACTICAL QUIET GENERATOR SET
0006 00
OPERATION UNDER USUAL CONDITIONS Continued
OPERATING PROCEDURES Continued
Starting Continued
WARNING
Operating the generator set exposes personnel to a high noise level. Hearing protection must be
worn when operating or working near the generator set when the generator set is running. Failure
to comply can cause hearing damage to personnel.
NOTE
Perform all DURING PMCS checks every four hours if TQG is operating continuously.
12. Perform all DURING PMCS requirements per WP 0012 00.
Stopping Procedure
1.
To remove load, on EMCP set AC CIRCUIT INTERRUPTER (5) switch to OPEN (down).
NOTE
ENGINE CONTROL switch may be set to MANUAL START to continue operation by turning
counterclockwise.
2.
Set ENGINE CONTROL (2) switch to COOL DOWN/STOP. This will allow generator set to operate with no load
applied for 5 minutes. The generator set will shut down automatically.
3.
Set ENGINE CONTROL switch to OFF/RESET.
4.
5.
Open rear left housing door and set DEAD CRANK SWITCH to OFF (WP 0005 00-13).
6.
Open battery compartment and set Battery Disconnect Switch to OFF (WP 0005 00-15).
END OF TASK
EMERGENCY STOPPING
1.
Press PUSH TO STOP EMERGENCY STOP (14) pushbutton to stop generator set.
2.
Set ENGINE CONTROL switch to OFF/RESET.
END OF TASK
0006 00-14