TM 9-6115-729-10
0006 00
OPERATION UNDER USUAL CONDITIONS Continued
OPERATING PROCEDURES Continued
Starting Continued
4.
Operate engine at no load for approximately 5 minutes or until coolant temperature reaches 100F (38C). If required,
load can be applied immediately.
5.
When TQG is running smoothly, fine tune VOLTAGE (3) and FREQUENCY (4) adjust potentiometers to required
values for voltage and frequency if necessary.
WARNING
High voltage power is available when the main contactor is closed. Avoid accidental contact with
live components. Ensure load cables are properly connected and the load cable door is shut before
closing main contactor. Ensure load is turned off before closing main contactor. Ensure that
soldiers working with/on loads connected to the generator set are aware that main contactor is about
to be closed before closing main contactor. Failure to observe this warning can result in severe
personal injury or death by electrocution.
6.
Set AC CIRCUIT INTERRUPTER (5) switch to CLOSED (up) and release to connect load to TQG.
7.
If operating with auxiliary fuel source, set AUX PUMP (6) switch to ON.
8.
On GSC panel keypad (7), press ENGINE METER (8) and check coolant temperature to be 170F to 200F (77C to
93C) and oil pressure to be 35 to 70 psi (241 to 483 kPa).
9.
On GSC keypad, press AC METER (9) to ensure voltage and frequency are still at rated values. Adjust if necessary.
10. Press POWER METER (10) on keypad and cycle through each phase position while observing current readings. If
more than rated load is indicated in any phase, reduce load.
11. On PARALLELING RECEPTACLES panel (11), press TEST (12) pushbutton on GROUND FAULT CIRCUIT
INTERRUPTER. Ensure that indicator window is red. Press RESET (13) pushbutton and ensure indicator is clear.
0006 00-13