ARMY TM 9-6115-672-14
AIR FORCE TO 35C2-3-444-32
MARINE CORPS TM 09244A/09245A-14
2-16
TABLE 2-5. OPERATOR PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS)
CAUTION
Engine oil and filter must be changed at a hardtime - 100 hours on initial
break-in. Failure to change oil and filter may void warranty.
B-BEFORE
D-DURING
A-AFTER
Interval
Item
No.
B
D
A
Item to
be inspected
Procedures
Check for and have
repaired or adjusted
as necessary
Equipment is
not ready/
available if:
GENERATOR SET
1
Housing
Check door, panels, hinges, and latches
for damaged, loose or corroded items.
Inspect air intake and exhaust grilles for
debris.
Cannot secure doors.
Cannot clear debris.
2
Identification Plates
Check to ensure identification plates are
secure.
3
Skid Base
Inspect skid base for cracks or corrosion. Skid base is cracked
or shows signs of
structural damage.
4
Insulating/Materials
Ensure that insulating materials are free
of damage, not missing, and not touching
moving or exhaust system parts.
__________
WARNING
Operating the generator set with any
access door open exposes personnel to
high noise level. Hearing protection
must be worn when operating or
working near the generator set with
any access door open. Failure to
comply can cause hearing damage to
personnel.
__________
WARNING
Fuels in the generator set are
flammable. Do not smoke or use open
flame when performing maintenance
Failure to comply can result in flames
and possible explosion and can cause
injury or death to personnel and
damage to the generator set.
TABLE 2-5. OPERATOR PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS)