ARMY TM 9-6115-671-14
AIR FORCE TO 35C2-3-446-32
MARINE CORPS TM 09249A/09246A-14
5-61
(10) If multimeter indicates resistance on any connection, stator windings are grounded and stator
must be replaced.
(11) Connect wires to voltage reconnection terminal board and remove tags. Refer to paragraph
5.8.2.
(12) Install moveable terminal board and protective cover on voltage reconnection terminal board.
Refer to paragraph 5.8.2.
(13) Install rear housing, paragraph 4.7.5.
(14) Connect negative battery cable to battery, and close BATTERY ACCESS door.
b. Replacement.
(1)
Shut down generator set, paragraph 2.11.2.
(2)
Remove generator assembly, paragraph 5.10.1.
(3)
Remove generator rotor assembly, paragraph 5.10.6.
(4)
Install generator rotor assembly, paragraph 5.10.6.
(5)
Install generator assembly, paragraph, 5.10.1.
5.11
MAINTENANCE OF SKID BASE.
__________
WARNING
When disconnecting or removing batteries, disconnect the negative lead
that connects directly to the grounding stud first. Disconnect the negative
end of the interconnection cable next. When installing batteries, reverse the
connection sequence. Failure to comply can cause serious personal injury.
5.11.1 Skid Base.
a. Inspection.
Inspect skid base for obvious signs of damage such as corrosion and dents.
b. Removal.
(1)
Shut down generator set, paragraph 2.11.2.
(2)
Remove engine and generator assembly, paragraph 5.4.2.
(3)
Remove fuel tank, paragraph 5.7.1.
(4)
Remove nuts (1, Figure 5-13), lockwashers (2), bolts (3), washers (4), and forklift guides (5)
from skid base.
(5)
Remove cable grommets (6 and 7) from skid base.
c. Repair.
Repair of skid base will be limited to corrosion control and spot welding minor cracks. If major