ARMY TM 9-6115-671-14
AIR FORCE TO 35C2-3-446-32
MARINE CORPS TM 09249A/09246A-14
3-12
TABLE 3-1. OPERATOR TROUBLESHOOTING (CONTINUED)
Yes
No
Not OK
OK
GENERATOR SET FAILS TO PARALLEL CORRECTLY (CONTINUED)
Continued from
previous page.
Check that both generator
voltage reconnect boards
are set to the same voltage
(Fig. 1-30)
Notify next higher level of
maintenance.
Are both generators
adjusted to the same
voltage?
Adjust generator sets to rated
voltage using VOLTAGE
ADJUST switch . (11, Fig 2-1)
Notify next higher level of
maintenance.