TM 9-6116-669-13&P
Section II. TROUBLESHOOTING
6.4 GENERAL,
The symptom index for EPP III lists faults associated with PDU assembly operation. Figures 5-1
through 5-10 provide a go/no-go flowchart for each malfunction. Each malfunction listed includes a
reference to the applicable figure that contains a chart to help you determine probable causes and
corrective actions to take. The symptom index cannot list all faults that may occur, or all possible
tests or inspections and corrective actions. If a malfunction is not listed or cannot be corrected by
the corrective actions listed, notify the next higher level of maintenance for assistance.
WARNING
Potential 150kw/208 VAC kw shock hazard with failure to adhere to
this warning. Contact with this high power could result in death or
severe injury. If the removal of one generator from the EPP III is
required, replace it with an extra generator if available. If the EPP
III must be operated with only one generator installed, insure that
all cables for the removed generator have the protective caps
properly installed prior to starting the remaining generator set.
Prior to energizing the equipment the operator must check for
exposed electrical terminals.
Always install protective covers on control and power cables when
cables are not connected.
Be sure to observe all Warning labels on equipment.
Potential 208 VAC shock hazard. Do not disconnect or connect
control or power cables while generator set 1 or 2 is running.
SYMPTOM INDEX
NO POWER TO ECS OR RS although Generator is Operating Normally.
Power Distribution Unit NOT OPERATING although Generator is Operating
Normally
Overload Shutdown of ECS or RS Load although Generator is Operating
Normally.
CANNOT SWITCH OVER from Generator 1 or 2 to Commercial Power
Converter.
CANNOT SWITCH OVER from Commercial Power Converter to Generator
Operation.
Figure 5-1
Figure 5-2
Figure 5-3
Figure 5-4
Figure 5-5
I
Change
1
5-3