INTERVAL
TM 9-6115-653-14&P
Table 3-2. Operator/Crew Preventive Maintenance Checks and Services (PMCS) (cont).
B BEFORED DURINGA AFTER
W WEEKLY
M MONTHLY
B
D
A
W
M
20
GENERATOR SET GAGES AND INSTRUMENTS
(cont)
i
Check that all lights on FAULT INDICATOR
Fault light will not go out
panel (26) are out during operation Check
when switch Is set to TEST
bulb operation with TEST or RESET switch on
or RESET position, then
panel
released All bulbs should
be lit when switch is in TEST
or RESET position
4885-018
21
FUEL TANK
a.
Fill set tank upon completion of operation
NOTE
Fuel system temperature must be above
freezing when draining water and sediment
b.
Open drain (27) and drain water and sediment
from fuel tank Into a suitable container Allow
to drain until fuel runs clean
ITEM
NO.
ITEM TO BE INSPECTED
PROCEDURE: CHECK FOR AND HAVE REPAIRED,
FILLED, OR ADJUSTED AS NEEDED
EQUIPMENT IS NOT
READY/AVAILABLE IF:
3-15