ARMY TM 9-6115-645-24
AIR FORCE TO 35C2-3-444-12
MARINE CORPS TM 09244A/09245A-24/2
TABLE 1-1. Tabulated Data - Continued
MEP-806A
9. Protection Devices - Continued:
c. Overspeed Switch:
(1) Element Trip and Reset
2200 ± 40 RPM
(2) Voltage Rating
28 VDC
(3) Current Rating
1 amp
d. Overvoltage Relay:
(1) Trip Point Conditions
153 ± 3 VAC for no less than
200 milliseconds (120 VAC
coil winding)
(2) Trip Point
No more than 1.25 seconds
after trip conditions exist
110 DIFFERENCES BETWEEN MODELS.
1-10.1
a.
b.
1-10.2
MEP-813A
2200 ± 40 RPM
28 VDC
1 amp
153 ± 3 VAC for no less than
200 milliseconds (120 VAC
coil winding)
No more than 1.25 seconds
after trip conditions exist
The differences between models of the generator sets covered in this manual areas follows:
Model MEP-806A is equipped with a 50/60 Hz generator, 50/60 Hz frequency meter, and frequency selector
switch.
Model MEP-816A is equipped with a 400 Hz generator and 400 Hz frequency meter.
Performance characteristics for the two models are shown in TABLE 1-2.
TABLE 1-2. Performance Characteristics
1. Voltage:
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
Voltage wave form
deviation factor:
Single voltage harmonics:
Voltage unbalance
Phase balance voltage
Voltage modulation
Voltage regulation
Short-term stability (30 seconds)
Long-term stability (4 hours)
Voltage drift (60°F (16°C) in 8-hour period)
Dip and rise for rated load
Recovery time
Dip for low power factor load
Recovery time
MEP-806A
5% (max)
2% (max)
5% of rated voltage (max)
1% of rated voltage (max)
1% (max)
1% (max)
1 % of rated voltage
2% of rated voltage
±1% (max)
15 % of rated voltage (max)
0.5 seconds
30% of no-load voltage (max)
0.7 seconds 95% of no-load
voltage
MEP-813A
5% (max)
2% (max)
5% of rated voltage (max)
1% of rated voltage (max)
1% (max)
1% (max)
1 % of rated voltage
2% of rated voltage
± 1 % (max)
12 % of rated voltage (max)
0.5 seconds
25% of no-load voltage (max)
0.7 seconds 95% of no-load
voltage
1-7