SECTION III.
MAINTENANCE PROCEDURES
3-3 GENERATOR SET INSPECTION
AND SERVICE.
3-3.1 Introduction.
This
section contains operator
maintenance procedures.
Deficiencies noted during
inspection which are beyond the
maintenance scope of the
operator shall be reported to
next higher maintenance level.
3-3.2 Batteries.
Battery acid can cause
burns to unprotected
skin.
WARNING
Batteries give off
flammable gas.
Do not
smoke or use open
flame when performing
maintenance.
Flames
and explosion could
result in personal
injury or death.
3-3.2.1
Inspection.
a.
Shut down generator
set, refer to
paragraph 2-9.2.
b.
Open battery access
door.
c.
Inspect for damaged
battery case,
corrosion, or damaged
and loose connections
on terminal cable,
and damaged or
missing battery caps.
WARNING
Batteries give off
flammable gas.
Do not
smoke or use open
flame when performing
maintenance.
Flames
and explosion could
result in personal
injury or death.
d.
Remove battery caps.
CAUTION
Electrolyte level must
cover battery plates
in all cells.
Failure
to observe this
caution can cause
damage to the battery.
NOTE
Electrolyte level
should be at bottom of
each cap cylinder.
e. Inspect electrolyte
level.
f. Perform service
procedures if
required.
g. Install battery caps.
h. Close battery access
door.
3-3.2.2 Service.
a.
Shut down generator
set, refer to
paragraph 2-9.2.
3-11