ARMY TM 9-6115-645-10
AIR FORCE TO 35C2-3-444-11
MARINE CORPS TM 09244A/09245A-10/1
TABLE 2-2. Malfunction Indicator Panel
KEY
CONNECTOR
FUNCTION
1
NO FUEL indicator
Lights when fuel level in fuel tank is below preset level.
2
COOLANT HIGH TEMP
Lights when engine coolant indicator temperature exceeds 2250 + 5° F (107 +±
30 F).
3
OVERVOLTAGE indicator
Lights when voltage in 120 volt generator coil exceeds 153 + 3 volts.
4
OVERSPEED indicator
Lights when engine speed exceeds 22d0 ± 40 RPM.
5
REVERSE POWER indicator
Lights when power flow into generator set exceeds 20 + 3 percent of rated
current.
6
OVER LOAD indicator
Lights when current in any phase exceeds 110 percent of rated current.
7
GROUND FAULT CIRCUIT
Tests GROUND FAULT CIRCUIT
INTERRUPTER TEST
INTERRUPTER.
Pushbutton
8
GROUND FAULT CIRCUIT
Indicates a ground fault condition.
INTERRUPTER
indicator
9
GROUND FAULT CIRCUIT
Rests GROUND FAULT CIRCUIT
INTERRUPTER RESET
INTERRUPTER.
Pushbutton
10
SHORT CIRCUIT indicator
Lights when generator set output in
any phase exceeds 425 + 25 percent
of rated current.
11
UNDER VOLTAGE indicator
Lights when voltage in 120 volt
generator coil winding drops below
99 ± 4 VAC.
12
PUSH TEST RESET LAMPS
Tests and resets fault indicator
switch
lamps.
13
LOW OIL PRESSURE
Lights when engine lubrication
indicator
systems pressure is less than 15 + 3
psi (103.4 + 20.7 kPa) during engine
operation.
14
Convenience Receptacle
Circuit breaker trips on when load
Overload Circuit
on convenience receptacle exceeds 10
Breaker (10-amp in-line
amps (fuse blows on generator sets,
fuse on generator sets,
contract number DAAK01-88-D-D082).
contract number DAAK01-88-D-D082)
Change 2 2-7