ARMY TM 9-6115-644-24AIR FORCE TO 35C2-3-446-12MARINE CORPS TM 09249A/09246A-24/1TABLE 2-6. Unit Troubleshooting - Continued.MALFUNCTIONTEST OR INSPECTIONCORRECTIVE ACTION25. NOVOLTAGEATCONVENIENCERECEPTACLE.Step 1.Open control panel and inspect circuit interrupter on side of Ground Fault CircuitInterrupter device.a.If device is tripped reset device for generator sets, contract numberDAAKO1-94-D-0036.b.For generator sets, contract number DAAK01-88-D-D082, check in-line fuse onblack lead of Ground Fault Circuit Interrupter.c.If device is not tripped, do Step 2.Step 2.Check Ground Fault Circuit Interrupter.a.If indicator is tripped, reset by pressing RESET button.b.If indicator is not tripped, do Step 3.Step 3.Check voltage across convenience receptacle.a.If voltage is present, replace convenience receptacle.b.If voltage is not present, do Step 4.Step 4.Check voltage across Terminals 4 and 6 no TB-5.a.If voltage is present, replace Ground Fault Circuit Interrupter.b.If voltage is not present, search for loose or broken wires or loose pinin connectors.2-26 Change 1