TABLE 2-6. Unit Troubleshooting - Continued.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
25. NO VOLTAGE AT CONVENIENCE RECEPTACLE.
Step 1.
Open control panel and inspect circuit interrupter on side of Ground Fault Circuit
Interrupter device.
a.
If device is tripped reset device for generator sets, contract number
DAAKO1-94-D-0036.
b.
For generator sets, contract number DAAK01-88-D-D082, check in-line fuse on
black lead of Ground Fault Circuit Interrupter.
c.
If device is not tripped, do Step 2.
Step 2.
Check Ground Fault Circuit Interrupter.
a.
If indicator is tripped, reset by pressing RESET button.
b.
If indicator is not tripped, do Step 3.
Step 3.
Check voltage across convenience receptacle.
a.
If voltage is present, replace convenience receptacle.
b.
If voltage is not present, do Step 4.
Step 4.
Check voltage across Terminals 4 and 6 no TB-5.
a.
If voltage is present, replace Ground Fault Circuit Interrupter.
b.
If voltage is not present, search for loose or broken wires or loose pin
in connectors.