Never attempt to start the generator set if it isnot properly grounded. Failure to observe thiswarning could result in serious injury or deathby electrocution.b. Determine voltage requirements of load and posi-tion voltage reconnection terminal boards of the twogenerator sets to the required voltage connection.E n s u r e F R E Q U E N C Y S E L E C T s w i t ch(MEP805A) for both generators are positioned forthe same load requirements.c. Identify one generator set as No. 1 and the other asNo. 2.d. Remove paralleling cable from storage box locatedinside battery compartment access door.ARMY TM 9-6115-644-10AIR FORCE TO 35C2-3-446-11MARINE CORPS TM 09249A/09246A-10/1e. Connect the paralleling cable between the two gen-erator sets. Connect the generator sets to the loadobserving the proper phase polarity.Do not close the AC CIRCUIT INTERRUPT-ER switch on either of the generator sets, norclose the load contactor at load until specifical-ly directed to do so. Closing any of these de-vices at any other time may severely damageone or both of the generator sets.2-10.3 Operation.a. Start each generator set, refer to paragraph 2-9.1.b. Rotate both VOLTAGE adjust potentiometers to ob-tain the same voltage indication on each set.Change 1 2-25