ARMY TM 9-6115-642-24
AIR FORCE TO 35C2-3-455-12
MARINE CORPS TM 09247A/09248A-24/2
Table 2-6. UNIT TROUBLESHOOTING - Continued.
MALFUNCTION
TEST OR INSPECTlON
CORRECTIVE ACTION
26.
NO VOLTAGE AT CONVENIENCE RECEPTACLE.
Step 1. Open control panel and Inspect circuit interrupter on side of Ground Fault Circuit Interrupter
device.
a.
If device is tripped, reset device for generator sets, contract number DAAK01-94-D-0036.
b.
For generator sets, contract number DMK01-88-D-D080, check in-line fuse on black lead
of Ground Fault Circuit Interrupter.
c.
If device is not tripped, do Step 2.
Step 2. Check Ground Fault Circuit Interrupter
a.
If indicator is tripped, reset by pressing RESET button
b.
If indicator is not tripped, do Step 3
Step 3. Check voltage across convenience receptacle
a
If voltage is present, replace convenience receptacle.
b.
If voltage is not present, do Step 4
Step 4. Check voltage across Terminals 4 and 6 on TB-5
a.
If voltage is present, replace Ground Fault Circuit Interrupter
b.
If voltage is not present, search for loose or broken wires or loose pin in connectors
Change 4 2-24.1/(2-24.2 blank)