ARMY TM 9-6115-642-10
AIR FORCE TO 35C2-3-455-11
MARINE CORPS TM 09247A/09248A-10/1
TABLE 3-1. Troubleshooting - Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
18.
AC CIRCUIT INTERRUPTER light fails to light when AC CIRCUIT INTERRUPTER switch is closed.
Step
1.
TEST AC CIRCUIT INTERRUPTER light by depressing. If light fails to light, refer to next
higher maintenance level.
Step
2.
Check load cables for proper connection. For proper connection of the load cables, refer to
paragraph 2-8.2. If correct go to Step 3.
Step
3.
Ensure load does not exceed generator rating. Decrease load, if load is correct, refer to next
higher maintenance level.
19.
No voltage at the Convenience Receptacle.
Step
1.
Open control panel and inspect circuit breaker on side of Ground Fault Circuit Interrupter
device. If tripped, reset device. Check fuse on black wire of Ground Fault Circuit
Interrupter for generator sets, contract number DAAK01-88-D-D080.
Step
2.
Check reset button for red band. If red band is visible, push reset button. If Ground Fault
Circuit Interrupter can not be reset, refer to next higher maintenance level.
Change 2 3-9