ARMY TM 9-6115-641-24
AIR FORCE TO 35C2-3-456-12
v.
Shut down generator set.
w. Disconnect jumper wire from terminal 3 of short circuit/overload relay and connect it to terminal 2.
x.
Repeat steps t and u.
y.
Shut down generator set.
z.
Disconnect jumper wire from terminal 2 of short circuit/overload relay and connect it to terminal 1.
aa. Repeat steps t and u.
ab. Shut down generator set.
ac. Replace short circuit/overload relay if any test is not as above.
ad. If no repair is needed, remove jumper wires and connect generator set wires to short circuit/overload relay,
over/under voltage relay and AC voltage regulator as tagged. Remove tags.
ae. Raise and secure control panel.
2-59