Inspection and Maintenance
Method
Item
Interval
d. Weigh, recharge if
30Days
Visual and
Fire Extinguisher
required, and perform all
Operational
(Cont)
inspections and mainte-
nance prescribed by the
manufacturer.
a. Check for cuts, cracks,
30 Days
visual
Tires
excessive or abnormal
wear on any surface.
b. Check for proper air
pressure (40 to 45 psig).
a. Check connectors for dirt
60 Days
Visual and
Controle Console
and Instrument
Operational
and corrosion.
Panel
b. Check harnesses and cable
for security of attachment
and chafing.
c. Check all external relay
connections for security
(power off).
d. Check ground connections
for security.
e. Check all insulation for
chafing and wear.
f. Check mounting bolts and
lugs for security of attach-
ment.
g. Check circuit breakers for
operation.
h. Check warning lights for
defective lamps.
Figure 4-4.
Table of Periodic Inspection and Maintenance (Sheet 2 of 8)
4-4