TM 5-6115-640-14&P
Table 2-1. Operator/Crew Preventive Maintenance Checks and Services - Continued
B - Before
D - During
A - After
W - Weekly
M - Monthly
INTERVAL
Item to be inspected
Procedure: check for and
Equipment is not
ITEM
have repaired, filled, or
ready/available if:
NO.
B
D
A
W
M
adjusted as needed
1
GENERATOR SET EXTERIOR
a. Check on, around, and be-
A Class III lubrication
neath the generator set (1)
oil or any class fuel
for fuel or oil leaks.
leak is detected.
b. Check that generator set
Not properly grounded.
grounds (2) are properly
installed, and grounding
connections are tight.
2
ENGINE OIL LEVEL
Open service access door, Panel'
5, and check oil filter dip-
stick (3) for proper oil level
Add oil as required.
2-9