Table 22-2. Operator/Crew Preventive Maintenance Checks and Services
NOTE: These checks are to be made in the order listed, within designated interval.
B - Before operation
A - After operation
M - Monthly
D - During operation
W - Weekly
1
ENGINE. Inspect engine for evidence of leak-
Class III oil leak or
age (oil or fuel) on, around, or under engine.
any fuel leak.
2
HARDWARE. Check for loose, damaged, or
missing hardware and parts.
3
AIR FILTER. Check for a serviceable and
Restricted or dirty
clean air filter.
filter.
4
FIRE EXTINGUISHER. Check for damaged
Contents indicator
or broken seal. Check valve and indicator.
is not in green area,
or valve is damaged,
seal is broken.
5
GROUNDING. Check to insure generator is
Generator set not
properly grounded. Check grounding connec-
properly grounded.
tions. Check ground cable and clamps.
6
FUEL FILTER. Inspect the fuel bowl, filter
Components are
element, filter head, and bowl gasket.
defective.
7
OIL LEVEL. Check oil level. Add oil as
Below add or above
required.
full mark.
8
GAGES AND INSTRUMENTS. Check for
proper generator operation.
a. VOLTMETER. Models MEP-0 1 6A and
Desired voltage can-
MEP-02 1A adjust for desired voltage. Rotate
not be obtained and
voltage selector switch to monitor the various
maintained.
output voltage combinations.
Model MEP-026A
Adjust for proper DC volts (must not exceed 28
V max).
b. FREQUENCY METER. Normal indica-
Indicates frequency
tion MEP-016A 59-61 MEP-021A 392-408.
too high or too low.