TB 9-6115-643-13
Section VII. REMOVAL INSTRUCTIONS
INSTRUCTIONS TO
UNIT MAINTENANCE FOR REMOVAL OF
WINTERIZATION KIT ON THE
15kW TACTICAL QUIET GENERATOR SET.
The following instructions have been provided so you can remove, Heater Kit, 15kW Generator Set
WARNING
Disconnect negative battery cable from right battery and the positive
battery cable from the left battery before doing the following
procedures. Failure to observe this warning could result in severe
personal injury or death.
WARNING
Before disconnecting any coolant lines, let generator cool from
operation, then relieve pressure by opening radiator cap carefully.
Coolant is hot and under pressure and may cause burns.
WARNING
Catch fuel in suitable container. Keep spilled fuel away from hot
engine and all fires. Wash with warm water after getting any on skin.
Fuel is highly flammable and is irritating to skin.
4-21.1
Removal Procedures.
INITIAL SETUP
Tools
Equipment Conditions
Tool Kit, General Mechanic's
Reference
Tool Kit, Automotive
Generator shut down
(Common No. I)
TM 9-6115-643-10
TM 9-6115-643-24
TM 9-2815-254-24
REMOVAL
1.
Turn heater and generator off.
2.
Open left and right access doors and disconnect negative battery cable from right battery and the positive battery cable
from the left battery.
3.
Drain generator coolant system in accordance with TM 9-6115-643-24.
4.
5.
Remove electrical leads from J6-16, 17, and 24, Figure 4-34.
6.
Remove control unit (1), Figure 4-33 from output box (2). Replace existing hardware.