TM 9-6115-729-24
UNIT (FIELD) LEVEL MAINTENANCE
TACTICAL QUIET GENERATOR 100 kW, 50/60 Hz MEP-807A/PU-807A
REPROGRAMMING
INITIAL SETUP:
Personnel Required
Equipment Condition
One
TQG is not operating and powered down
References
TM 9-6115-729-24P
REPROGRAMMING DVR PARAMETERS FOR VOLTAGE AND FREQUENCY CHANGE
The following procedure is used if the voltage and frequency settings for the generator set must be changed
because of mission requirements. When that occurs, the reconnection board must be repositioned and the DVR
must be reprogrammed for specified frequency and voltage. Note that the GSC OP-5 parameters must be
reprogrammed, also.
1. Set Battery Disconnect Switch to ON.
2. Set DEAD CRANK SWITCH to NORMAL.
3. On EMCP, set ENGINE CONTROL Switch (ECS) to COOL DOWN/STOP.
4. Select reprogramming data from Table 1 below according to the desired output voltage and desired
frequency. Mission requirements will define requirements.
NOTE
All six of the DVR PARAMETERS must be changed or verified.
DESIRED OUTPUT
DVR PARAMETER NUMBER
VOLTS
HERTZ
:01
:02
:03
:04
:05
:06
120/208
60
217
1.0
0
347
4.34
58.8
120/208
50
205
1.0
0
289
3.61
49.8
240/416
60
434
2.0
0
174
4.34
58.8
240/416
50
410
2.0
0
145
3.61
49.8