• Home
  • Download PDF
  • Order CD-ROM
  • Order in Print
Testing - TM-9-6115-644-24_243
FIGURE 4-1. Test Circuit

TM-9-6115-644-24 Generator Set Tactical Quiet 15 Kw 50/60-400 Hz MEP-804A (60 Hz) MEP-814A (400 Hz) Manual
Page Navigation
  220    221    222    223    224  225  226    227    228    229    230  
ARMY TM 9-6115-644-24 AIR FORCE TO 35C2-3-446-12 MARINE CORPS TM 09249A/09246A-24/2 4-1-4 Removal. a.   Shutdown   generator   set. b. Open battery access door and disconnect negative battery cable. c. Release control panel by turning two fasteners and lower control panel slowly. d. Tag and disconnect AC voltage regulator (2, FIGURE 4-3) electrical leads. e. Remove screws (1) and AC voltage regulator (2). 4-1-5  Installation. CAUTION The components of the AC voltage regulator kit are not interchangeable. Ensure the part number of the component to be installed is the same as the removed component. Failure to observe this caution will result in equipment damage. a. Install AC voltage regulator (2, FIGURE 4-3) with screws (1). b. Connect electrical leads and remove tags. c. Raise and secure control panel. d. Connect negative battery cable. Close battery access door. 4-2 SHORT   CIRCUIT/OVERLOAD   RELAY 4-2-1 Testing CAUTION Make  sure  negative  battery  cable  is  disconnected  prior  to  removing  wires.  Failure  to  ob- serve this caution could result in equipment damage. a. Remove  short  circuit/overload  relay,  paragraph  2-56-3. b.  Install  relay  in  test  circuit  (FIGURE  4-?) c. Set multimeter for OHMS and check for open circuits between terminals 5 and 6,9 and 10,. Check for closed circuits between terminals 7 and 8, 11 and 12. If relay fails the above test, replace relay. If relay tests good, continue with remainder of test. d. Activate power source G1. Adjust voltage to 0 volts. e. Place switch S2 in the “A” position and close S1. f. Slowly increase output voltage of G1 to 6.18 VAC (110% rated load). Leave G1 at this setting for 10 minutes. Relay should not trip, circuits should remain as indicated in step c above. g. Set multimeter for OHMS and check across terminals 5 and 6 while slowly increasing output voltage of G1 to 7.30 VAC (130% rated load). The relay should trip within 8+/- 2 minutes. When relay trips circuit 5 and 6 should close, circuit 7 and 8 should open. 4-4







Western Governors University

Privacy Statement
Press Release
Contact

© Copyright Integrated Publishing, Inc.. All Rights Reserved. Design by Strategico.