TM 9-6150-226-13
NOTES:
1. THIS FIGURE ILLUSTRATES ASSEMBLY OF THE M200 A/P FEEDER CENTER, CONNECTOR J1.
2. ALL DIMENSIONS ARE IN INCHES, WITH METRIC EQUIVALENTS IN PARENTHESES.
3. REMAINING WIRES ARE REMOVED FOR CLARITY.
4. CUT AND REMOVE WIRE INSULATION AS INDICATED.
5. CRIMP ELECTRICAL CONTACT PINS TO WIRES FOR POSITIONS AS FOLLOWS:
ITEM
WIRE
WIRE
POSITION
NO.
SIZE
LENGTH
A
C
N
G1
G2
G3
G4
4 and 6
4 and 6
4 and 6
5 and 6
7,8, and 9
7,8, and 9
7,8, and 9
7,8, and 9
4/0
4/0
4/0
4/0
4
4
4
4
19.75 (501.7 MM)
21.00 (533.4 MM)
21.00 (533.4 MM)
11.75 (298.5 MM)
17.75 (450.9 MM)
17.75 (450.9 MM)
18.25 (463.6 MM)
18.00 (457.2 MM)
6. ELECTRICAL CONNECTOR (ITEM 2) IS FURNISHED WITH THE FOLLOWING:
COVER (ITEM 1)
GASKET (ITEM 3)
ELECTRICAL CONTACT PINS (ITEMS 4,5, AND 8)
7. ASSEMBLE CONNECTOR SO KEYS AND PINS ALINE AS INDICATED.
FIGURE F-26. PDISE 200-amp input connector assembly. (sheet 2 of 2)
F-72
Change 1