SYMPTOM
34.
Coolant Temperature Too High.
MALFUNCTION
Excessive Load.
CORRECTIVE ACTION
STEP 1.
Ensure that the load is not excessive. Check load current and kW on GSC
display. If load is excessive go to step 2.
STEP 2.
On EMCP set Engine Control Switch to OFF/RESET. Set Battery Disconnect
Switch to OFF. Set DEAD CRANK SWITCH to OFF.
STEP 3.
Redistribute or disengage loads as required.
STEP 4.
Verify the problem has been resolved.
MALFUNCTION
Radiator.
CORRECTIVE ACTION
STEP 1.
On EMCP set Engine Control Switch to OFF/RESET. Set Battery Disconnect
Switch to OFF. Set DEAD CRANK SWITCH to OFF.
STEP 2.
Ensure that the engines exhaust does not heat the radiator.
STEP 3.
Ensure the air inlet area of the radiator is not obstructed.
STEP 4.
Check the fins of the radiator for damage or obstructions. Repair/ clean as
STEP 5.
Verify the problem has been resolved.
MALFUNCTION
Low Coolant Level.
CORRECTIVE ACTION
STEP 1.
On EMCP set Engine Control Switch to OFF/RESET. Set Battery Disconnect
Switch to OFF. Set DEAD CRANK SWITCH to OFF.
STEP 2.
Allow generator set to cool and check coolant level. Add coolant as required.