TM 9-6115-729-24
0011
TROUBLESHOOTING FAILURES WITHOUT FAULT CODES - Continued
SYMPTOM
7.
Display of Current on GSC is Inaccurate.
MALFUNCTION
Setpoint Incorrect.
CORRECTIVE ACTION
STEP 1.
On EMCP set ENGINE CONTROL switch to COOL DOWN/STOP. Set Battery
Disconnect Switch to ON. Set DEAD CRANK SWITCH to NORMAL.
STEP 2.
View and record value of setpoint P021. If value does not agree with
STEP 3.
View and record value of setpoints in OP8 (WP 0085).
STEP 4.
Open EMCP and record value of bar code setpoints located on ATB A5.
a. If values of OP8 setpoints do not agree with bar code setpoints marked on
b. If setpoints agree, on EMCP set ENGINE CONTROL switch to OFF/RESET.
Set Battery Disconnect Switch to OF. Set DEAD CRANK SWITCH to OFF.
c.
STEP 5.
On EMCP set ENGINE CONTROL switch to COOL DOWN/STOP. Set Battery
Disconnect Switch to ON. Set DEAD CRANK SWITCH to NORMAL.
STEP 6.
View and record value of setpoints in OP8.
a. If value does not agree with programmed setpoint, reprogram GSC
b. Retest the system.
STEP 7.
Verify the problem has been resolved.
0011-10