ARMY TM 9-6115-672-14
AIR FORCE TO 35C2-3-444-32
MARINE CORPS TM 09244A/09245A-14
4-43
TABLE 4-4. UNIT TROUBLESHOOTING (CONTINUED)
Replace automatic voltage
regulator (see para. 4.8.23).
Is fault cleared?
Not OK
OK
Not OK
FAULT INDICATOR DISPLAYS WARNING -
OVERVOLTAGE OR SHUTDOWN - OVERVOLTAGE
FAULT INDICATOR displays WARNING -
OVERVOLTAGE or SHUTDOWN - OVERVOLTAGE.
Check for defective or loose
connections on voltage adjust
switch. Refer to Wiring
Diagram, FO-3.
Repair or replace defective
or loose connections. Refer to
Wiring Diagram, FO-3.
Test VOLTAGE ADJUST
switch (see para. 4.8.10).
Replace VOLTAGE
ADJUST switch
(see para. 4.8.10).
Troubleshoot voltage regulator
circuit for breaks or loose
connections. Refer to
Schematic, FO-1.
OK
Repair or replace defective or
loose connections. Refer to
Wiring Diagram, FO-3.
Is fault cleared?
Not OK
OK
Notify next higher level of
maintenance.
No
No