ARMY TM 9-6115-672-14
AIR FORCE TO 35C2-3-444-32
MARINE CORPS TM 09244A/09245A-14
3-11
TABLE 3-1. OPERATOR TROUBLESHOOTING (CONTINUED)
Not OK
Not OK
OK
Yes
No
OK
Not OK
Not OK
OK
Not OK
OK
No
Yes
GENERATOR SET FAILS TO PARALLEL CORRECTLY
Generator set fails to parallel correctly.
Check FAULT INDICATOR
on CIM display screen. Is a
fault displayed? (Fig 2-2)
Go to troubleshooting section
corresponding to fault displayed.
See Symptom Index, page 3-1.
Check that parallel cable
is connected properly (see
para. 2.12.2).
Connect parallel
cable properly (see
para. 2.12.2).
Check that STATUS/CONTACT
POSITION indicator on both
generator sets reads CLOSED.
(Fig 2-2)
Momentarily hold AC CIRCUIT
INTERRUPTER switch (10, Fig 2-1) on
generator set(s) in CLOSED position
until STATUS/CONTACT POSITION
indicator reads CLOSED. (Fig 2-2)
Check that load cables
are installed properly
(see para. 2.9.2).
Install load cables
properly (see para.
2.9.2).
Is generator set a
50/60 Hz unit? (Fig.
1-3)
Check that FREQ gage on
CIM display screen
indicates proper Hz setting.
(Fig. 2-2)
Check that FREQUENCY
SELECT switch (22, Fig 2-1)
is in the same position on both
units.
Set FREQUENCY
SELECT switch on
both generators to the
same position.
Use FREQUENCY
ADJUST switch (9, Fig. 2-1) to
obtain proper Hz setting.
Continued on next page.
OK