ARMY TM 9-6115-671-14
AIR FORCE TO 35C2-3-446-32
MARINE CORPS TM 09249A/09246A-14
3-3
TABLE 3-1. OPERATOR TROUBLESHOOTING (CONTINUED)
No
OK
OK
Not OK
Not OK
Yes
ENGINE CRANKS BUT FAILS TO START
Engine cranks but fails to start.
Inspect air cleaner
assembly (see para. 3.3.3).
Is ambient temperature above
40°F(4°C)?
Pull EMERGENCY
STOP switch to out
(deactivated) position.
Service air cleaner
assembly (see para.
3.3.3).
Inspect/service fuel filter/water
separator (see para. 3.3.7).
Use ETHER START switch (7,
Fig 2-1) to assist in starting
engine in cold weather, below
40°F (4°C). Does Engine start ?
Notify next higher
level of maintenance.
Check FAULT INDICATOR
on CIM display screen. Is a
fault displayed? (Fig 2-2)
Activate FAULT RESET Switch
(12, Fig 2-1) on DCS control
panel. Does fault clear?
Go to troubleshooting
section corresponding to
fault displayed. See
Symptom Index, page 3-1.
Is EMERGENCY
STOP switch (3, Fig
2-1) pushed in?
No
Is speed control unit
DC POWER LED (15,
Fig 2-3) lit?
Yes
No
No
Notify next higher
level of maintenance.
Yes
No
Yes
No
Activate FAULT RESET Switch
(12, Fig 2-1) on DCS control
panel. Does fault clear?
No
Notify next higher
level of maintenance.