TABLE 2-5. OPERATOR PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS)
(continued)
B-BEFORE
D-DURING
A-AFTER
Interval
Item
No.
B
D
A
Item to
be inspected
Procedures
Check for and have
repaired or adjusted
as necessary
Equipment is
not ready/
available if:
16
Air Cleaner
Assembly
Inspect air cleaner assembly and piping
for loose or damaged connections.
Piping connections
are loose.
Check restriction indicator for indication
of clogged air cleaner element (Refer to
Figure 3-1).
Clogged element is
indicated.
ELECTRICAL
SYSTEM
__________
WARNING
DC voltages are present at generator
set electrical components even with
generator set shut down. Avoid
shorting any positive terminal with
ground/negative. Failure to comply
can cause injury to personnel and
damage to equipment..
__________
WARNING
Batteries give off a flammable gas. Do
not smoke or use open flame when
performing maintenance. Failure to
comply can cause injury or death to
personnel and equipment damage due
to flames and explosion.
__________
WARNING
Battery acid can cause burns to
unprotected skin. Avoid contact with
battery acid. Failure to comply can
cause injury to personnel.
17
Batteries
Inspect electrolyte level (wet cell
batteries only).
Electrolyte level is
below battery plates.
18
Battery Cables
Inspect cables and connectors for
corrosion and loose, damaged, or
missing parts.
Battery cables are
loose, damaged, or
missing.