ARMY TM 9-6115-671-14
AIR FORCE TO 35C2-3-446-32
MARINE CORPS TM 09249A/09246A-14
2-6
TABLE 2-2. CIM DISPLAY SCREEN CONTROLS AND INDICATORS
KEY
CONTROL OR INDICATOR
FUNCTION
1
GEN VOLTAGE indicators
Indicates generator output voltage for each of the three phases.
2
BATTERY VDC indicator
Indicates charge status of both generator set DC batteries
(VDC).
3
GEN CURRENT indicators
Indicates generator output current (amps) for each of the three
phases.
4
FAULT INDICATOR display
Displays fault indications as they occur. Specific warnings and
instructions related to a fault are displayed simultaneously in
the MESSAGES display. See Table 2-3 for the list of possible
faults.
5
DELTA VAC gage
Indicates generator set output voltage versus bus voltage. Used
prior to operating in parallel with another unit. Used to monitor
system prior to parallel operation to ensure generator and bus
voltage are balanced within 5 volts before closing contactor to
bus.
6
MESSAGES display
Displays warnings and instructions in the form of operator
messages related to faults displayed in FAULT INDICATOR
display.
7
WATER TEMP virtual meter
Indicates generator set cooling system water temperature (°F).
8
BATTLE SHORT CIRCUIT status
indicator
Indicates whether generator set is in battle short mode or not.
ON indication means battle short circuit is energized.
9
CONTACTOR POSITION status
indicator
Indicates whether contactor is open or closed.
10
DISPLAY MODE FULL/MAIN
switch
When FULL/MAIN button is selected with the keypad, CIM
display screen toggles between FULL and MAIN modes and
button changes to show name of mode currently displayed.
11
SHUTDOWN COMPUTER
EXIT button
When EXIT button is selected with the keypad, the DCS
software shuts down so the CIM can be safely deactivated.
This will also shut down the generator set if it is running.
12
BATTERY AMPS virtual meter
Indicates input current of generator set DC batteries (amps).
13
OIL PRESSURE virtual meter
Indicates engine oil pressure (psi).
14
BUS VOLTAGE indicators
Indicate voltage on output bus. The GEN VOLTAGE and BUS
VOLTAGE indicators must match within five volts, each phase,
to perform paralleling operation.
15
VOLTAGE gage
Indicates generator set voltage output (VAC).
16
FREQ gage
Indicates generator set frequency output (Hz).
17
POWER gage
Indicates generator set power output (kW).
18
FUEL LEVEL gage
Indicates amount of fuel in fuel tank (percent remaining).