ARMY TM 9-6115-670-14&P
2-7
Table 2-2. Operator Preventative Maintenance Checks and Services (PMCS) for Auxiliary Power Unit,
10 kW, 120/240 VAC, 60 Hz
Location
Item
No.
Interval
Item to
Check/Service
Procedure
Not Mission
Capable If:
1
Before
Generator Set
Check for loose, broken or missing hardware.
Check for fluid leaks.
Check for any loose wires or broken meters.
Level III fluid
Leak exists.
Before/
During
Ground Cable and
Connection
Inspect ground rod and cable for loose
connections, breaks, damage and corrosion.
Check for paint.
Cable is
missing or
damaged or
components
are not free
of paint.
2
Before
Engine radiator
Check coolant level. Coolant level should be
halfway between "FULL" and "LOW" marks on
radiator overflow tank; add coolant if needed (para
3.8.).
Coolant level
is well below
radiator port.
3
Before
Radiator hose
Check for leaks.
Class III leak
exists
(para 2.2.5,
4.7.4.).
4
Before
Radiator overflow
tank
Check coolant level. Coolant level should be
halfway between FULL and LOW marks.
(Figure 2-2)
WARNING
Hot coolant is under pressure. Do not remove radiator
cap when engine is hot. Allow engine to cool completely
before removing radiator cap. Once cooling has
occurred, loosen cap slightly to relieve any excess
pressure before removing the cap completely. Failure to
observe this warning could result in burns or injury to
personnel.
CAUTION
Be sure to close radiator cap securely. If
cap is loose or improperly closed, coolant
may leak out and the engine could
overheat