TM 9-6115-664-13&P
Table 4-2. Unit Preventive Maintenance Checks and Services for Generator Set MEP-952B
Item
No.
Interval
Location:
Item to
Procedure
Not Fully Mission
Capable If:
Check/
Service
1
Quarterly
Overall
a. Inspect for cracks, leaks, dents, and
Class m oil or any fuel
Generator
corrosion.
leaks are present.
Set
Significant cracks exist
b. Inspect for loose hardware.
in enclosure or components.
2
Quarterly
Local
a. Inspect for security of attachment.
Control or indicator is
Control
Check for obvious damage.
damaged to the point it
Panel
will affect safe operation.
b. Test switches for smooth operation.
Check for normal indications.
c. Perform electrical check of system using
control panel test points (Table 4-4).
3
Quarterly
Remote
Inspect fault indicators for proper
Control or indicator is
Control
operation using press to test button.
damaged to the point it
Panel
will affect safe operation.
4
Quarterly
Fuel
a. Inspect fuel filter water separator for
Leaks are present or
System
damage. Inspect for water and drain.
lines are damaged. Fuel
float valve leaks.
b. Inspect fuel float valve bowl for cracks
or leaks.
c. Inspect all fuel lines for cuts, tears, loose
connections, or evidence of leakage.
5
Quarterly
Engine
a. Inspect engine fuel piping for damage,
Leaks are present or
kinks, evidence of leakage.
hoses are damaged.
Loose connections.
b. Inspect hoses for evidence of wear,
cracking, and deterioration. Check
connections for tightness.
4-9