TM 9-6115-647-14&P
Table 3-2. Operator Preventive Maintenance Checks and Services (Cont).
B-Before
D-During
A-After
W-Weekly
M-Monthly
Item
Item To Be Inspected,
Equipment Is Not
No.
B
D
A
W
M
Procedure: Check For And Have
Ready/Available If:
Repaired, Filled, or Adjusted As Needed
22
GENERATOR SET GAGES AND INSTRUMENTS
(cont)
i. Check that all lights on fault indicator panel (42) Fault light will not go out
are out during operation. Check bulb operation when switch is set to TEST
with TEST or RESET switch on panel.
or RESET position, then
released. All bulbs should
be lit when switch is in TEST
or RESET position.
23
FUEL TANK
WARNING
Do not smoke or use open flame in vicinity of
power unit while refueling generator set.
a. Fill set tank and auxiliary tank upon completion
of operation.
NOTE
Fuel system temperature must be above
freezing when draining water and sediment.
3-17