TM 9-6115-646-14&P
Table 3-2. Operator/Crew Preventative Maintenance Checks and Services (PMCS) (cont.)
B - Before
D - During
A - After
W - Weekly
M - Monthly
INTERVAL
ITEM TO BE INSPECTED
ITEM
PROCEDURE: Check for and have repaired,
Equipment is Not
NO
B
D
A
W
M
filled, or adjusted as needed
Ready/Available If:
20
GENERATOR SET GAGES AND INSTRUMENTS
(cont.)
i.
Check that all lights on FAULT INDICATOR
Fault light will not go out
panel (30) are out during operation Check
when switch Is set to TEST
bulb operation with TEST or RESET switch
or RESET position, then
on panelreleased All bulbs should
be lit when switch is in TEST
or RESET position
4885-018
21
AIR RESERVOIR
a.
Visually Inspect air reservoir (31) for damage or
leaks.
WARNING
Airstream from open draincock could cause
eye injury Wear protective goggles when
working with air under pressure Failure to
do so could result in eye Injury
b.
Open draincock (32) to drain accumulated
moisture.
3-15