TM 9-6115-646-14&P
Table 3-2. Operator/Crew Preventive Maintenance Checks and Services (PMCS) (cont).
Interval
Item
Item To Be Inspected
Equipment Is Not
No.
B D
A
W
M
Procedure:
Ready/Available If:
1
GENERATOR SET EXTERIOR
a. Check on, around, and beneath generator set
A Class III coolant or lubrica-
for fuel or oil and coolant leaks.
tion oil leak or any class fuel
leak is detected.
b. Check that generator set ground is properly
Generator set ground wire is
installed and grounding connections are
not properly installed.
tight.
c. Manually open and close radiator louver doors
Louver doors do not
to check for proper operation.
operate correctly.
2
COOLANT
Check coolant level. Coolant should be two inches
Coolant level is below
below overflow in radiator filler neck (1).
recommended level.
Change 1 3-5