ARMY TM 9-6115-644-24
AIR FORCE TO 35C2-3-446-12
MARINE CORPS TM 09249A/09246A-24/2
b.
Install screws (14), washers (32), and nuts (13).
c.
Connect electrical leads and remove tags.
d.
Raise and secure control panel.
e.
Connect negative battery cable. Close battery access door.
2-27 BATTERY CHARGE AMMETER.
2-27-1
a.
b.
2-27-2
a.
b.
c.
d.
e.
f.
2-27-3
a.
Inspection.
Shut down generator set.
Inspect ammeter for broken lens, cracked housing and other damage.
Testing.
Start and operate generator set at rated voltage and frequency.
Release control panel by turning two fasteners and lower control panel slowly.
Set multimeter for DC volts and connect across BATTERY CHARGE ammeter terminals. Connect
positive lead to positive terminal and negative lead to negative terminal if you observe or think
battery is charging. Multimeter should indicate up to 50 mv (25 mv equals + 10 amps on BATTERY
CHARGE ammeter).
Reverse multimeter leads if you observe or think battery is discharging. Multimeter should indicate
up to 25 mv (25 mv equals -10 amps on BATTERY CHARGE ammeter).
If multimeter indicates millivolt reading and BATTERY CHARGE ammeter is not within + 10% of
equal ampere reading, or ammeter is not indicating, replace BATTERY CHARGE ammeter.
Raise and secure control panel.
Removal.
Shut down generator set.
b.
Open battery access door and disconnect negative battery cable.
Change 1 2-59