Close oil drain valve and remove oil fill cap.
d. Fill engine with proper lube oil in accordance with TABLE 2-3 to FULL mark on dipstick. Lubrication system
capacity is 5.9 quarts (5.6 liters).
e.
Install oil fill cap.
f.
Close left side engine access door.
2-2
General Set Installation.
2-2.1
General.
WARNING
Exhaust discharge contains deadly gases. Do not operate generator sets in en-
closed areas unless exhaust discharge is properly vented outside. Severe per-
sonal injury or death due to carbon monoxide poisoning could result.
a.
Ensure that installation site is as level as possible.
b. Provide adequate ventilation to prevent recirculation of hot air exhausted from generator set.
c .
Place generator set within twenty-five feet (7.4 meters) of auxiliary fuel supply.
d. Refer to FIGURE 2-1 for minimum enclosure clearance measurement requirements and FIGURE 2-2 for
base mounting measurements.
TABLE 2-2. DIESEL FUEL
TABLE 2-3. LUBRICATING OIL
2-3