ARMY TM 9-6115-642-24
AIR FORCE TO 35C2-3-455-12
MARINE CORPS TM 09247A/09246A-24/2
NOTES:
1. Refer to TM 9-6115-642-24P for materials required.
2. Transducer wiring is not polarity sensitive, so position of terminals is not important.
PROCEDURES:
1. Strip 0.25 inch of insulation from end of each transducer (1) lead.
2. Crimp male terminal (2) on one wire and female terminal (3) on other wire.
FIGURE D-15. Transducer Assembly (P/N: 88-20480)
D-16