General. The NATO slave receptacle can be
used to start the generator set when batteries are
discharged.
2-19.2
2-21
a.
b.
c
Connect one end of NATO slave cable to fully
charged 24 VDC system and other end to
discharged generator sets NATO slave receptacle.
start discharged generator set.
Refer to Paragraph 2-10 for engine starting
procedures.
Remove NATO slave cable after generator set
Starts.
2-20
2-20.1
General. Depressing the EMERGENCY
STOP pushbutton will stop the generator set.
NOTE
The generator set cannot be restarted without
resetting the EMERGENCY STOP pushbutton
and turning MASTER SWITCH to OFF
position.
a.
b.
Continued operation using the BATTLE
SHORT switch can result in damage to the
generator set.
NOTE
If any emergency situation requires continued
operation of the generator set, the BATTLE
SHORT switch is used to override all the safety
devices except the short circuit devices, and
EMERGENCY STOP function.
NOTE
BATTLE SHORT switch must be OFF to start
generator set.
Start generator set if set is not running. Refer to
paragraph 2-10.
Lift cover on BATTLE SHORT switch and position
switch to ON.