TM 5-6115-628-14&P
Table 3-2. Operator/Crew Preventive Maintenance Checks and Services (PMCS) - CONT.
B - Before
D - During
A - After
W - Weekly
M - Monthly
18
3-14
GENERATOR SET GAGES AND
INSTRUMENTS - CONT
h. Check coolant temperature gage (23)
for 170° to 200°F (76.7° to
93.3°C) indication.
i.
Check that all lights on fault in-
dicator panel (24) are out during
operation. Check bulb operation
with TEST or RESET switch on paneI.
Temperature exceeds
200°F (93.3°C).
Fault light will not go
out when switch is set
to TEST or RESET posi-
tion, then released,
All bulbs should be lit
when switch is in TEST
or RESET position.